Flowline LU78 EchoSwitch User Manual

Page 7

Advertising
background image

Rev A 

MN300282 

7 of 34 

GETTING STARTED (continued) 

Step Four 

TOP‐LEVEL MENU Descriptions 
UNITS – Allows end user to select the units for configuration and operation.   

o

Select  between  Inches,  Centimeters,  Feet,  Meters  or 
Percent.   

o

Press EXIT to return to the TOP‐LEVEL MENU. 

TANK – Allows the end user to configure the operational range 

for the switch as well as the 4‐20 mA output signal.   

o

HEIGHT  –  Distance  from  the  transducer  face  to  the 
bottom of the tank.  

o

FILL‐H  –  Maximum  fill  height  of  the  liquid  from  the 
bottom of the tank. 

o

Note: The 4 and 20 mA points are set by setting these 
two points.   

The  20  mA  point  is  at  the  Fill‐H  and  the  4  mA 

point is at the bottom of the tank. 

 The 4 and 20 mA set points cannot be reversed. 

o

Press Exit to return to the TOP‐LEVEL MENU 

o

Note:  if UNITS is set to Percent, then TANK will not appear.  To view TANK, set UNITS to any of the 
following: Inches, Centimeters, Feet or Meters
 

RELAY 1, RELAY 2 or RELAY 3 – Allows end user to configure the function and operation of each relay.  

Each  relay  has  a  small  black  circle  that  appears  when  the  relay  is  energized.    When  the  relay  is  de‐
energized, the black circle disappears.  

o

PUMP  –  Pump  operation  allows  for  two  separate  level  set  points  (Relay  ON  and  Relay  OFF).  
Choose between the EMPTY or FILL operation.  Both operations require setting a level for ON and 
another level for OFF 

EMPTY – used to control a pump that empties a tank.   

 

 Typically, Relay ON is the HIGH set point and Relay OFF the LOW set point.  Relay will 

energize at the high set point (ON) and remain on until the level reaches the low set 
point (OFF).  It will remain off until the level returns to the high set point (ON). 

 
 

 