Flowline LU78 EchoSwitch User Manual

Page 26

Advertising
background image

26 of 34 

MN300282 

Rev A 

INSTALLATION 

Step Seven 

The  EchoSwitch®  should  always  be  mounted  perpendicular  to  the  liquid  surface  and  installed  using  the 
provided  Viton®  mounting  gasket.    Make  sure  that  the  fitting  and  transmitter  threads  are  not  damaged  or 
worn.    Always  hand‐tighten  the  transmitter  within  the  fitting.    Perform  an  installed  leak  test  under  normal 
process  conditions  prior  to  system  start  up.    Note:  The  preferred  mounting  fitting  for  the  LU77  Series  is  the 
LM52‐1400 (2” thread x 1” thread) reducer bushing. 

Mounting Guide 
1. Do not mount at an angle. 
2. Liquid should never enter the dead band. 
3. Side Wall: 

a. Mount at least 3” from the side wall. 
b. For LU77 Series ‐ mount at least 2” from the side 

wall. 

4. Do not mount where obstacles will intrude into sensor’s 

beam width. 

a. Beam Width: 3” (7.6cm) diameter [2” (5cm) for 

LU77 series]. 

5. Do not mount in a vacuum. 
6. Avoid mounting in the center of a dome top tank. 
7. In cone bottom tank, position the sensor over the 

deepest part of the tank. 

Installation in existing fittings:  If the existing fitting is larger 
than  the  threads  of  the  EchoSwitch®,  select  a  reducer 
bushing  such  as  the  LM52‐1400  (2”  thread  x  1”  thread)  or 
LM52‐2400 (3” thread x 2” thread). 

 

LM52‐1400 

 

LM52‐2400 

Do not install at 

angle relative to 

the liquid. 

Do not install 

within 2” of tank 

sidewall. 

(3” for DL34 series) 

Do not install with 

objects in the 

beam. 

Do not install in 

applications with 

vacuum. 

 


Metal  Tanks  (LU77  Series  Only):    Flowline  ultrasonic  sensors  have  been  optimized  for  use  in  non‐metallic 
fittings.   

1. For best performance, avoid the use of metallic fittings. 

a. Use a plastic 2” x 1” reducer bushing, such as the LM52‐1400 or a plastic 1” flange, such as the 

LM52‐1850 for metallic tanks. 

2. While  installations  directly  into  a  1”  metal  fitting  are  not  recommended,  acceptable  results  may  be 

obtained  if  the  1”  fitting  is  a  half  coupling  in  form  and  the  outer  diameter  of  the  coupling  is  tightly 
wrapped in vinyl tape to dampen vibration. 

 

 