CONFIGURATION (cont.) 

Step Five 

How to Time Alternate relays:  This function is only operational when two or more relays are configured as 
pumps  performing  the  same  function  (either  filling  or  emptying).    This  function  is  useful  when  a  complete 
cycle of the pumps cannot be guaranteed such as a continuous inflow to a sump.  Thus one pump may run 
longer than the other pump.  To insure equal wear of both pumps, the alternating cycle can be set up on a 
timer.  Thus the lead and lag pumps will be switched based on time rather than a cycle basis. 

1. Make  sure  at  least  two  relays  are  in  the  same 

mode.   
a. Example:  two  relays  are  set  as  PUMPs  that 

FILL  or  three  relays  are  set  as  PUMPs  that 
EMPTY).   

b. If  this  condition  is  not  met,  M‐PLEX  will  not 

appear. 

2. In TOP‐LEVEL MENU mode, select M‐PLEX. 
3. Select DUPLEX or TRIPLX. 
4. Select A‐TIME. 
5. Select HOURS. 
6. Using  the  UP  and  DOWN  buttons,  set  the 

Alternating Time in Hours.   
a. Alternating  Time  can  be  set  from  0  to  600 

hours. 

7. To  enter  the  value,  press  and  hold  SELECT  for  2 

seconds and release.  SAVED will display. 

8. Select EXIT to return to TOP‐LEVEL MENU. 

 
 

 