APPENDIX (continued) 

Step Eight 

Troubleshooting 

PROBLEM 

 

  SOLUTION 

TANK does not appear on 
the main menu 

Units  function  is  set  for  PERCENT  on  EchoSwitch®:    When  Units  is  set 
for  PERCENT,  the  TANK  function  is  disabled.    To  re‐enable  TANK, 
change units to INCHES, CM, FEET or METERS. 

Display always jumps to 
the LOST condition 

Check  the  dimensional  configuration  (Height  and  Fill‐H)  of  the 
EchoSwitch®.  Make sure that the Fill‐H setting corresponds to the full 
level  of  liquid  (from  the  bottom  up)  and  not  the  distance  from  the 
sensor to the liquid (top down). 

M‐PLEX does not appear 
on the main menu 

None of the relays are configured the same:  M‐PLEX will only appear 
when 2 or 3 relays are configured as the same function.  For example, 
two or more relays are configured as Pumps that Auto Fill.  M‐PLEX will 
not appear if a relay is configured as an Auto Empty Pump and an Auto 
Empty Valve.   

Display shows FULL 

Level  of  liquid  is  above  the  FILL_H  setting:    Check  the  FILL_H  setting, 
making sure the FILL_H setting is high enough so the level of liquid is 
below the FILL_H setting 

Display shows EMPTY 

Level of liquid is beyond the HEIGHT setting:  Check the HEIGHT setting, 
making sure the HEIGHT setting is low enough so the level of liquid is 
above the HEIGHT setting 

Pumps or Valves do not 
alternate 

1. M‐PLEX is set for NO‐ALT or A‐TIME is set above 0: 

a. If  M‐PLEX  is  set  for  NO‐ALT,  then  the  relays  will  not  alternate.  

Change M‐PLEX to either DUPLEX or TRIPLX to begin alternation.  

b. If A‐TIME is set for anything above 0 hours, then the pumps will 

only  alternate  after  the  A_TIME  set  has  been  reached.    For 
example,  if  A‐TIME  is  set  for  3  hours,  then  the  relays  will  only 
switch after each 3 hour period.  To alternate after each cycle, 
change A‐TIME to 0 hours  

2. The ON levels for the relays are set to the same setting.  Change the 

ON set point to another value. 

3. The  DELAY  is  set  for  a  period  of  time  that  has  not  been  reached.  

Example: if delay was set to 600, you must wait 10 minutes before 
the relay will trigger. 

Relay closes, but does not 
open again 

An inductive kick may be holding the relay closed.  If switching 24 VDC, 
make sure a diode has been installed to act as a snubber. 

Relay chatters on and off 
repeatedly 

Most likely the turbulence in the tank is causing the chatter.  Increase 
the Hysteresis setting to correct.  

Relay does not initially 
switch. 

Check  the  DELAY  setting  for  the  relay.    The  delay  time  must  be  met 
before the relay switches.  Example: if delay was set to 600, you must 
wait 10 minutes before the relay will trigger. 

 
 

 