ELECTRICAL 

Step Six 

Input  Power  and  Relay  Connections:    The  EchoSwitch®  is  powered  from  95  to  250  VAC  power.    Power  is 
applied to the L1 and L2 terminals.  Typically, Hot is applied to L1 and Neutral to L2.  The Gnd terminal should 
be connected to a solid earth ground to help shield the sensor from external EMI/RFI interference. 

The  EchoSwitch®  features  three  60  VA,  2A  max  relays.    Relay  1  has  both  the  Normally  Open  and  Normally 
Closed contacts available.  Relays 2 and 3 have the Normally Open contacts available.  All three relays have 
their commons connected and are isolated.  The example below shows Relay 2 wired NO.  Make sure to select 
a relay state that is fail‐safe and takes into account when power is lost to the EchoSwitch®.   

The switching of heavy inductive loads such as pump motors can create voltage spikes in the many thousands 
of  volts.    It  is  recommended  that  the  power  to  the  EchoSwitch®  and  to  the  coils  of  the  isolation  relays  be 
sourced from a main that is not switching inductive loads as shown below. 

 

Note #1 – Isolate power to instrument from power to load (pumps, etc.) as much as possible by running 

power to the sensor directly from main power source. 

Relay Configuration: 

 

All three (3) EchoSwitch® relays share the common relay terminal.  

Relay #1 is a Form “C” SPDT contact.   

o

It  is  useful  for  controlling  a  valve  which  requires  a  contact  to  open 
and a contact to close.   

Relays #2 & #3 are Form “A” SPST contacts.   

o

These  two  relays  (#2  &  #3),  in  addition  to  relay  #1,  can  be  used  for 
controlling valves, pumps or alarms. 

Note:    Because  all  three  (3)  relays  share  the  common  relay  terminal,  the 
relays must all switch the same power. 

 

 

 