CONFIGURATION (cont.) 

Step Five 

How to set Relay Fail‐Safe / LOST:  In the event the sensor does not receive an echo, the Fail‐Safe Output or 
LOST  setting  can  be  set  to  turn  each  relay  ON,  OFF  or  HOLD  (to  last  state)  to  achieve  the  desired  fail‐safe 
condition. During fail‐safe, the display will read LOST. 

1. In TOP‐LEVEL MENU mode, select SAFE.
2. Select R1 (Relay 1), R2 (Relay 2) or R2 (Relay 3). 
3. Select ON, OFF, or HOLD. 
4. Select EXIT to return to TOP‐LEVEL MENU. 

Power  Outage:    If  power  to  the  EchoSwitch®  is 
removed  (intentionally  or  accidentally),  the  relays 
will return to the normal state.  Thus, in Relay 1, NC 
terminal will be closed and NO terminal will be open.  
Also, the NO terminals in relays 2 and 3 will also be 
open.  Make sure that the de‐energized state is the 
safe  state  in  your  system  design.    The  EchoSwitch® 
does use non‐volatile memory so any power loss will 
not affect the settings or configuration of the sensor. 

How to select Fail‐Safe Current Output / LOST:  In the event the sensor does not receive an echo, the Fail‐Safe 
Current  Output  or  LOST  setting  can  be  set  to  output  a  current  of  4mA,  21mA  or  Hold  (last  known  value).  
During fail‐safe, the display will read LOST. 

1. In TOP‐LEVEL MENU mode, select SAFE.
2. Select OUTPUT. 
3. Select 4mA, 21mA, or HOLD. 
4. Select EXIT to return to TOP‐LEVEL MENU. 

 

 