CONFIGURATION (cont.) 

Step Five 

How to Alternate two relays:  Alternate enables EchoSwitch® to use two relays to alternate after each cycle.  
The  configuration  of  Alternate  is  identical  to  Duplex  with  the  exception  of  the  Backup  level  is  at  a  setting 
where the level will never achieve set point.  To begin, configure two relays in the same mode (ex: two relays 
are set as PUMPs that FILL or two relays set as PUMPs that EMPTY).  Be sure to set one relay with an ON Set 
Point at the Primary Level and the other relay ON Set Point at the Backup Level.  Setting the relays with the 
same ON level will have cause both relays to turn on at the same time.  The Backup level must be set to a level 
out of range (level will never reach this setting).  Once this is completed, see the steps below.  Example below 
shows two relays (A and B) used to Auto Empty a tank: 

 

1. Make  sure  at  least  two  relays  are  in  the  same 

mode for pumps.   
a. If  this  is  not  true,  then  M‐PLEX  will  not 

appear. 

2. In TOP‐LEVEL MENU mode, select M‐PLEX. 
3. Select DUPLEX. 

a. If  three  relays  are  configured  in  the  same 

mode, continue to step 4. 

b. If  only  two  relays  are  configured,  jump  to 

step 5. 

4. Select R1_R2 (Relay 1 & 2), R2_R3 (Relay 2 & 3) 

or R1_R3 (Relay 1 & 3). 
a. EchoSwitch®  will  allow  you  to  select  two  of 

three relays to duplex.   

5. Select EXIT to return to TOP‐LEVEL MENU. 

 
 

 