GETTING STARTED (continued) 

Step Four 

o

ALARM  –  Alarm  operation  allows  for  a  single  set  point  (Relay  ON  and  OFF  at  the  same  level).  
Choose between HIGH and LOW operation.  Both operations will require a single set point and a 
setting for the Hysteresis (HYSTER) 

 

HIGH – used to control a High Level alarm.  Relay will energize (ON) when the level is above 

the setting and will de‐energize (OFF) when the level falls below the setting plus the added 
distance from the hysteresis (HYSTER). 

LOW – used to control a Low Level alarm.  Relay will energize (ON) when the level is below 

the setting and will de‐energize (OFF) when the level rises above the setting plus the added 
distance from the hysteresis (HYSTER). 

HYSTER – Used to reduce chatter by creating a hysteresis or differential for the Alarm set point.  

The HYSTER value will adjust the OFF position of the Alarm setting by the HYSTER value.  

SAFE – Each relay can be individually configured to its own fail‐safe setting.  Choose between ON, OFF or HOLD. 

o

ON – Energizes the relay when a fail‐safe condition occurs 

o

OFF – De‐energizes the relay when a fail‐safe condition occurs 

o

HOLD – Keeps the relay in its current state when a fail‐safe condition occurs 

o

OUTPUT – Sets the 4/20 mA output state when the echo is lost.  The options are 4mA, 21mA and 
hold last value. 

M‐PLEX – when two or three relays are configured as pumps, they can be inter–connected to alternate 

between each cycle.   

o

M‐PLEX is only available when 2 or more relays are set for pumps.   

o

M‐PLEX  will  not  appear  when  only  1  relay  is  set  for  a  pump  or  when  the  relay  functions  do  not 
match (ex: Relay 1 set for a filling pump and Relay 2 set for an emptying pump).   

o

Selecting NO‐ALT will turn OFF the M‐PLEX.  

HELP – Provides setup information, the ability to reset the EchoSwitch® and a simulation mode to test the 

relay function 

o

SETUP – Will display the setting for all functions of EchoSwitch® 

o

RESET – Will reset the EchoSwitch® back to its original factory setting 

o

SIM‐T – SIM (ulation)‐T(est) will allow the end user to simulate changes to level to verify the relay 
settings.  Using the UP and DOWN buttons will increase 

o

TEST  P  –  This  is  a  production  test  feature  used  by  the  factory  to  confirm  operation.    This  mode 
should only be used when supervised by a Flowline representative.
 

RUN – Returns the unit to normal measurement and control mode 