Flowline LU78 EchoSwitch User Manual

Page 31

Advertising
background image

Rev A 

MN300282 

31 of 34 

APPENDIX (continued) 

Step Eight 

Simulation  (SIM‐T):   This mode enables  the end user to  simulate changes in level  without having the level of 
liquid move.  The display will simulate level of liquid and will turn the relays ON and OFF according to how they 
were configured.  Example:  If Relay 1 is set as a High Alarm with an ON setting for 100.0 inches and a Hysteresis 
of 2.0 inches, then when the display goes above 100.0, Relay 1 will energize and when the level falls below 98.0, 
Relay 1 will de‐energize.  Use this function to test the wiring and to verify the sensor’s configuration.   

Please  note:  Simulation  mode  will  energize  and  de‐energize  all  configured  relays.    Any  devices  wired  to  the 
relays will become active during simulation mode. 

1. In TOP‐LEVEL MENU, select HELP. 
2. Select SIM‐T. 
3. The display will start at 0.0.   

a. Press  and  hold  the  UP  button  to  begin 

increasing the level of liquid.   

b. Use  the  DOWN  button  to  simulate  the 

lowering of liquid in the tank. 

c. To  increase  speed,  hold  the  SELECT  button 

while hold the UP or DOWN keys. 

4. Test  the  functionality  of  the  relays  confirming 

their ON and OFF levels. 

5. To exit, press and hold the SELECT key. 
6. Select EXIT to return to TOP‐LEVEL MENU. 

Test Parameters:  This mode runs diagnostic tests that confirm operation of EchoSwitch®.  This is a production 
test feature used by the factory to confirm operation.   
1. In TOP‐LEVEL MENU, select HELP. 
2. Select TEST P. 
3. TEST P will perform the following test: 

a. Run a LCD Check 
b. Turn ON all three relays 
c. Turn OFF all three relays. 

4. TEST P will also list the following settings: 
5. Select EXIT to return to TOP‐LEVEL MENU. 

Note:    This  mode  should  only  be  used  when 
supervised by a Flowline representative. 

 