Configuring an "onoff" control function – Burkert Type 8619 User Manual

Page 52

Advertising
background image

50

Adjustmentandcommissioning

8.10.13. configuring an "onoff" control function

This function is used to set the on/off control.

A conductivity control system can be combined with the "time dosing" function (see chap. 8.10.15) to carry out a
prebleed step before dosing.

Once the function has been configured and activated, the result "Fx:" calculated is available in the list of
process variables on the "M0:MAIN" board. This list appears in the output configuring, user view config-
uring and datalogging menus to:

• Assign the result "Fx:" calculated to a physical output (analogue, AO, or digital, DO) (see chap. 8.10.22

and 8.10.22).

• Display the result "Fx:" on one of the user defined "Ux" views: see chap. 8.10.8.

• Logging the values of "Fx:" using the datalogger: see chap. 8.10.18.

Setpoint (SP)

prebleed

ONOFF

fallback

position

"Time dosing"

function ("Dos. St.")

Process input

(PV)

result (Fx: CMD1)

System

switch

Figure 38 :

"ONOFF" function

1

13:40

1

0

0

2010/06/29

F2:ONOFF

250.0

µS/cm
PV

500.0

µS/cm
SP

0.00

%
CMD1

No Link

F3 Dos.St

Value of the process variable chosen

Value of the setpoint
Result of the ONOFF function
No associated time dosing

press this dynamic key to enter the setpoint value.

SETP

MENU

Figure 39 :

Example of a view of an "ONOFF" function in Process level with no associated time dosing

Type 8619

english

Advertising