Figure 62 – Burkert Type 8619 User Manual

Page 75

Advertising
background image

73

Adjustmentandcommissioning

P

1

and P

2

are the values associated with a current of 4 mA or 20 mA respectively.

If P1 is higher than P

2

, the signal is inverted and the range P

1

-P

2

corresponds to the range for the 20-4

mA current.

mA

0

20

4

P

2

P

1

Figure 62 :

4-20 mA current depending on the PV selected

FILTER: Choose the level of damping for the fluctuations of the current value for each current output. See Figure
29.
DIAG. EVENTS: Choose to emit a current of 22 mA on the current output selected when an "error" event related
to diagnostics (see chap. 8.12.4 to 8.12.6) is generated by the multiCELL or allow the current output to operate
normally (choose "none").

See also "If you encounter problems" in chap. 9.3.

Type 8619

english