Adjustmentandcommissioning

0%

100%

Fx: CMD1

PV parameter

Setpoint

non-inverted mode

hysteresis

0%

100%

Fx: CMD1

PV parameter

Setpoint

inverted mode

hysteresis

Figure 40 :

Hysteresis operating, non-inverted and inverted

MAXONTIME: Enter the max. authorised duration of output control: after this period, the output is deactivated.
PREBLEED: Define (choose "ON") or not (choose "OFF") the ONOFF function for controlling a conductivity
function as a prebleed function associated with a time dosing function ("Time Dosing": see chap. 8.10.15). When
prebleed is activated, enter the prebleed setpoint value:

-

PBLIMIT1: enter the prebleed setpoint for channel 1 on the associated "Time Dosing" function.

-

PBLIMIT2: enter the prebleed setpoint for channel 2 on the associated "Time Dosing" function.

Prebleed lowers the conductivity of the fluid to a value below the standard setpoint value of the ON/OFF con-
troller. When activated, the prebleed setpoint, "PBLIMITx", overrides the standard setpoint of the controller.

A prebleed setpoint value lower than or equal to the conductivity setpoint value of the ON/OFF controller
must be entered.

0

1

conductivity

standard setpoint

t

CMD1

time dosing cycle, priority on the

controller

prebleed setpoint

"PBLIMITx"

"OFF"

Title "Tdos state"

(see Figure 42)

"OFF" : pending dosing

"BLEED" : prebleed currently underway

"ON" : dosing currently underway

"WAIT" : waiting time; see page 64

"BLEED"

"ON"

"WAIT"

change of status if "PBLIMIT" is reached or
"MAXONTIME" exceeded

Figure 41 :

Combination of "ONOFF" and "TIME DOSING" functions on a conductivity measurement

Type 8619