Burkert Type 8619 User Manual

Page 78

Advertising
background image

76

Adjustmentandcommissioning

HIGH: Choose the value of the high switching threshold of the output.
INVERT: Invert the output or not.
DELAY: Choose the value of the time-out before switching for each digital output. This is valid for both output
thresholds. Switching is only done if one of the thresholds, high or low (functions "High" or "Low"), is exceeded
for a duration longer than this time-out.
configuring in "Window" operating

The output status changes as soon as any threshold (low or high) is reached..

ON

OFF

contact

Low High process input ("PV")

not inverted

ON

OFF

contact

Low High process input ("PV")

inverted

Figure 64 :

Window operating

PV: Choose the process input associated with the output selected.
LOW: Choose the value of the process input for the low switching threshold of the output.
HIGH: Choose the value of the process input for the high switching threshold of the output.
INVERT: Invert the output or not.
DELAY: Choose the value of the time-out before switching for each output. This is valid for both output
thresholds. Switching is only done if one of the thresholds, high or low (functions "High" or "Low"), is exceeded
for a duration longer than this time-out.
configuring in "fastpWm" operating

This mode is used to control a proportional solenoid valve.

T1

T2

0

1

T1

T1

T1

T2

T2

t

not inverted

output

inverted

output

T1

T2

T1

T1

T2

T2

t

0

1

T2 = period, constant = 1/frequency

T1 varies

Figure 65 :

"FastPWM" operating

PV: Choose the process input associated with the output selected.
LOW: Choose the value of the process input ("PV") corresponding to 0% PWM.
HIGH: Choose the value of the process input ("PV") corresponding to 100 % PWM.
INVERT: Invert the output or not.
FREQUENCY: Choose the value of the output frequency (= 1/T2), from 2 to 2000 Hz.

Type 8619