Setting the parameters of the current outputs, And p, Range of the input signal process variable – Burkert Type 8619 User Manual

Page 74: Refer to chap. 8.9 to access parameters menu, English

Advertising
background image

72

Adjustmentandcommissioning

0V: Enter the value of the previously selected process variable, which is associated to a 0 V input voltage. Instead
of being entered, the value can be automatically determined using the function "PV calibration" in the menu "Cali-
bration -> Mx:Inputs -> AI1 or AI2". See chap. 8.11.4.
5/10V: Enter the value of the previously selected process variable, which is associated to a 5/10 V input voltage.
Instead of being entered, the value can be automatically determined using the function "PV calibration" in the
menu "Calibration -> Mx:Inputs -> AI1 or AI2". See chap. 8.11.4.

P

1

and P

2

are the values of the process variables which are associated to the selected input range.

P

2

P

1

4................................20 mA

0................................................20 mA
0................................................5 V
0................................................10 V

Range of the input signal

Process variable

Figure 61 :

Configuring an analogue input

FILTER: Choose the level of damping for the fluctuations of the current or voltage value. See Figure 29.

8.10.21. setting the parameters of the current outputs

Refer to chap. 8.9 to access Parameters menu.

This is
when the
device is be-
ing parame-
tered............
....................

This is
when the
device is be-
ing parame-
tered............
....................

M0:Outputs

AO1/AO2

PV:

1)

M1:

M0:MAIN

Mx:

...

4mA:

ENTERING

20mA:

ENTERING

Diag. events:

None

22mA

Filter:

Fast

None

Slow

Parameters

Mx:Outputs

1)

The choices offered depend on the modules fitted and/or the options activated. See chap. 8.10.4 and chap. 8.16.

PV: Choose the process input associated with the current output.
4mA: Choose the value of the process input previously selected, associated with a current of 4 mA, for each
current output. See Figure 62.
20mA: Choose the value of the process input previously selected, associated with a current of 20 mA, for each
current output. See Figure 62

Type 8619

english

Advertising