Adjustmentandcommissioning

configuring in "pWm" operating

This mode is used to control an "on/off" actuator.

T1

T1

T1

T1

T2

T2

T2

t

not inverted

output

HIGH

LOW

T1

T2

T1

T1

T2

T2

t

inverted

output

HIGH

LOW

T2 = period, constant

T1 varies

Figure 66 :

"PWM" operating

PV: Choose the process input associated with the output selected.
LOW: Choose the value of the process input ("PV") corresponding to 0% PWM.
HIGH: Choose the value of the process input ("PV") corresponding to 100 % PWM.
INVERT: Invert the output or not.
PERIOD: Choose the value of period T2 in seconds.
MIN ON TIME: Choose the minimum value of T1 in seconds.
configuring in "pfm" operating

This mode is used to control a dosing pump, for example.

not inverted

output

T2

T1

T2

T2

T2

T2

t

HIGH

LOW

T2

T2

T2

T2

T2

T1

t

inverted

output

HIGH

LOW

T1 = period, constant

T2 varies

Figure 67 :

"PFM" operating

PV: Choose the process input associated with the output selected.
LOW: Choose the value of the process input corresponding to the min. frequency.
HIGH: Choose the value of the process input corresponding to the max. frequency defined in "MAX. FREQ."
below.