Burkert Type 8793 User Manual

Page 11

Advertising
background image

11

Technical Data

Type 8792, 8793

7.4 Rating plats

Description of standard rating plate:

Type

8792 24V / DC

P = 1,4 ... 7 bar

Remote IP65/IP67

Tamb 0°C...+60°C

D-74653 Ingelfingen

Ser.-Nr.: 001000
00177689 W12LL

Operating voltage / Control

Exemple:

Identification number

Degree of protection

Nominal pressure

Ambient temperature

Serial number,

Fig. 2:

Exemple standard rating plate

Description of additional plate for Ex approval:
Devices, which may be used in the explosion-protected area, are
identified by the additional plate for the Ex approval.

II 3 G Ex nA IIC T4

II 3 D Ex tD A22 T135°C

Warning:

1. Do not open under
explosive atmosphere
2. In Hazardous Areas the surface
may only be cleaned with a wet towel

Fig. 3:

Additional plate for Ex approval

7.5 Mechanical data

Dimensions

See data sheet

Material

Housing material

Plastic-coated aluminium

Other external parts

Stainless steel (V4A), PC, PE, POM,
PTFE

Sealing material

EPDM, NBR, FKM

Mass

approx. 1.0 kg

7.6 Electrical data

Protection class

3 in accordance with VDE 0580

Connections

2 cable glands (M20 x 1.5) with screw-
type terminals 0.14 – 1.5 mm

2

or circular

plug-in connector

Operating voltage

24 V DC ± 10% max. residual ripple 10%

Power consumption

< 5 W

Input data for actual value signal
4 ... 20 mA:

Input resistance 180 Ω
Resolution

12 bit

Frequency:

Measuring range 0 ... 1000 Hz
Input resistance 17 kΩ
Resolution

1‰ vom Messwert,

Input signal > 300 mV

ss

Signal form Sine, rectangle, triangle

english

Advertising