Electrical Installation

Type 8792, 8793

14.6.2 Output signals to the control centre

(e.g. PLC)
(required for analogue output and/or
binary output option only)

Connect terminals according to the model (options) of the
positioner.

Terminal Configuration

On the device
side

External circuit / Signal level

83 +

Binary output
1

83 +

24 V / 0 V, NC / NO
specific to operating voltage
GND (terminal GND)

85 +

Binary output
2

85 +

24 V / 0 V, NC / NO
specific to operating voltage
GND (terminal GND)

31 +

Analogue
feedback +

31 +

+ (0/4 ... 20 mA or 0 ... 5 / 10 V)
completely galvanically isolated

32 –

Analogue
feedback
GND

32 –

GND Analogue feedback

Tab. 12: Terminal assignment; output signals to the control centre

14.6.3 Operating voltage

Terminal Configuration

On the device
side

External circuit /
Signal level

+24 V

Operating voltage + +24 V

GND

24 V DC ± 10 %
max.

residual ripple

10 %

GND

Operating voltage
GND

Tab. 13: Terminal configuration; operating voltage

14.6.4 Terminal assignment for external

position sensor (for remote model
only)

Connection of the digital, contact-free position sensor
Type 8798:

Terminal Configuration

On the
device side

External circuit / Signal level

S +

Supply sensor
+

S +

+

Remote
Sensor
Type
8798*

For
assignment
of the wire
color see
“Tab. 15”

S –

Supply sensor

S –

A

Serial interface
A-line

A

A-line

B

Serial interface
B-line

B

B-line

Tab. 14: Terminal configuration; position sensor Type 8798

Positioner
Terminal

Wire color Type 8798
Cable type 1

Cable type 2

S +

brown

brown

S –

white

black

A

green

red

B

yellow

orange

Tab. 15: Assignment of the wire color, position sensor Type 8798