1 safety end positions – Burkert Type 8793 User Manual

Page 27

Advertising
background image

27

Fluid connection

Type 8792, 8793

Procedure:

Apply supply pressure (1.4 – 7 bar) to the supply pressure con-
nection P.

For single-acting actuators (control function A and B):

Connect one working connection (A1 or A2, depending on
required safety end position) to the chamber of the single-acting
actuator.
Safety end positions see chapter“13.1.1”.

Seal a working connection which is not required with a plug.

For double-acting actuators (control function I):

Connect working connections A1 and A2 to the respective
chambers of the double-acting actuator
Safety end positions see chapter “13.1.2”.

Important information for perfect control behaviour!
This ensures that the control behaviour is not extremely
negatively affected in the upper stroke range on account of
too little pressure difference.
• keep the applied supply pressure at least 0.5 – 1 bar

above the pressure which is required to move the pneu-
matic actuator to its end position.

If fluctuations are greater, the control parameters measured
with the

X.TUNE function are not optimum.

• during operation keep the fluctuations of the supply

pressure as low as possible (max. ±10%).

13.1 Safety end positions

The safety end position following failure of the auxiliary electrical
power depends on the fluidic connection of the actuator to the
working connections A1 or A2.

13.1.1 Single-acting actuators

Actuator system

Safety end positions after failure of the

electrical

auxiliary power

pneumatic
auxiliary power

up

down

down

Connection
according to
“Fig. 17”

down

up

Connection
according to
“Fig. 18”

Control function A

up

down

up

Connection
according to
“Fig. 17”

up

down

Connection
according to
“Fig. 18”

Control function B

Tab. 6: Safety end positions - single-acting actuators

english

Advertising
This manual is related to the following products: