7 terminal assignment for cable gland, Process controller type 8793 – Burkert Type 8793 User Manual

Page 36

Advertising
background image

36

Electrical Installation

Type 8792, 8793

Connection of a potentiometric position sensor:

Terminal Configuration

On the
device
side

External circuit

Potentiometer 1 1

Potentio-
meter

Center tap 2

2

Center tap

Potentiometer 3 3

Tab. 16: Terminal assignment; potentiometric position sensor

When the operating voltage is applied, the positioner is operating.

Now make the required basic settings and actuate the automatic
adjustment of the positioner. The procedure is described in chapter
“16.2 Starting-up Type 8792”

14.7 Terminal assignment for cable

gland - process controller Type
8793

First connect the process controller as described in chapter
“14.6 Terminal assignment for cable gland - positioner Type
8792”
.

14.7.1 Terminal assignments of the process

actual value input

Input
type*

Terminal Configuration

On the
device side

External
circuit

4 ... 20 mA
- internally
supplied

actual value

1

+24 V Input
transmitter

1

2

3

GND

Trans-
mitter

GND

2

Output from
transmitter

3

Bridge to GND
(Terminal GMD from
operating voltage)

4

not used

GND

GND from operating
voltage

4 ... 20 mA
- externally
supplied

actual value

1

not used

2

Process actual +

2

+ (4...20 mA)

3

Process actual –

3

GND

4

not used

english