Burkert Type 8793 User Manual

Page 43

Advertising
background image

43

Start-Up

Type 8792, 8793

Input the input signal (INPUT)

In the

INPUT menu option select the input signal for the set-

point value.
(4 ... 20 mA, 0 ... 20 mA, 0 ... 10 V or 0 ... 5 V).

INPUT

4-20 mA

0-20 mA

0-10 V

0-5 V

Selection of the
input signal

EXIT

ENTER

SELEC

X.TUNE

press for approx. 3 s

Process level (values are displayed)

MENU

Einstellebene

ADD.FUNCTION

EXIT

Fig. 25: Operating structure INPUT; Input the signal

Automatic adjustment of the positioner to the operating
conditions (X.TUNE)

WARNING!

Danger due to the valve position changing when the X:TUNE
function is run!
When the

X.TUNE function is run under operating pressure, there

is an acute risk of injury.

Never run X.TUNE while the process is running!

▶ Secure system from unintentional activation!

NOTE!

An incorrect supply pressure or incorrectly connected
operating medium pressure may cause the controller to be
wrongly adjusted!

▶ Run X.TUNE in each case at the supply pressure available in

subsequent operation (= pneumatic auxiliary power).

• Run the

X.TUNE function preferably without operating medium

pressure to exclude interference due to flow forces.

The following functions are actuated automatically:
• Adjustment of the sensor signal to the (physical) stroke of the

actuator used.

• Determination of parameters of the PWM signals to control the

solenoid valves integrated in Type 8792/8793.

• Setting of the controller parameters of the positioner. Optimization

occurs according to the criteria of the shortest possible transient
time with simultaneous freedom from overshoot.

english

Advertising
This manual is related to the following products: