3 start-up type 8793 – Burkert Type 8793 User Manual

Page 44

Advertising
background image

44

Start-Up

Type 8792, 8793

To stop

X.TUNE, press the left or right selection key

STOP

.

Procedure:

Key

Action

Description

MENU

press for

approx. 3 s

Change from process level

setting level

/ Select

X.TUNE

RUN

Hold down

as long as countdown
(5 ...) is running

During the automatic adjustment
messages are displayed indi-
cating the progress of the
X.TUNE

"TUNE #1... X.TUNE ready".

Press any key

Return to main menu (MAIN)

EXIT

press

Change from setting level

process level

Tab. 24: Automatic adjustment of X.TUNE

You have to exit the main menu by pressing the left selection
key

EXIT

before the modified data is saved in the memory

(EEPROM). During the save process the save symbol is
indicated on the display.

16.3 Start-up Type 8793

To be able to operate the positioner as a process controller, perform
the following steps:

1. Setting up the position controller:

Description see “16.2.1 Specifying the standard settings”

2. Setting up the process controller:

Enter the

P.CONTROL auxiliary function into the main menu

(MAIN) via the configuration menu (

ADD.FUNCTION).

Key

Action

MENU

press for approx. 3 s

/ Select

ADD.FUNCTION

ENTER

press

/ Select

P.CONTROL

ENTER

press

EXIT

press

The

P.CONTROL function is now activated and entered in the

main menu (MAIN).

Tab. 25: Enter the P.CONTROL auxiliary function into the main menu

(MAIN)