1 basic settings of the process controller – Burkert Type 8793 User Manual

Page 45

Advertising
background image

45

Start-Up

Type 8792, 8793

16.3.1 Basic settings of the process

controller

In the main menu (MAIN) select the P.CONTROL function and
make the basic settings.

EXIT

ENTER

16

M A I N

P.CONTROL

ADD.FUNCTION

P.TUNE

EXIT

EXIT

PID.PARAMETER

SETUP

DBND 0,1 %

PV-INPUT

KP 0,00

PV-SCALE

TN 0,5

SP-INPUT

TV 0,0

SP-SCALE*

X0 0,0 %

P.CO-INIT

FILTER 0

P.CONTROL

ENTER

ENTER

ENTER

EXIT

Main menu

* The SP SCALE function

appears only when the
external preselected set-
point value (external) menu
option is activated under
SP INPUT.

Fig. 26: Operating structure - basic settings of the process controller

P.CONTROL - settings:

PID.PARAMETER Parameter settings of the process controller

DBND 0,1 % Insensitivity area of the PID process controller

KP 0,00 Amplification factor of the process controller

TN 0,5

Reset time

TV 0,0

Hold-back time

X0 0,0 %

Operating point

FILTER 0

Filtering of the process actual value input

SETUP

Setting up the process controller:

PV-INPUT

AIndication of the signal type for process
actual value

PV-SCALE

Scaling the process controller

SP-INPUT

Type of the set-point value default (internal or
external)

SP-SCALE*

Scaling the position controller (for external set-
point value default only)

P.CO-INIT

Enables a smooth switchover between AUTO-
MATIC and MANUAL operating state

Tab. 26: Basic settings of the process controller

Parameters can be set automatically with the aid of the

P.TUNE

function (description see “Operating instructions for Type
8792/8793”).

english

Advertising