Electrical Installation

Type 8792, 8793

Input
type*

Terminal Configuration

On the
device side

External
circuit

Frequency
-internally
supplied

actual value

1

+24 V sensor supply

1

+24 V

2

Clock input +

2

Clock +

3

not used

4

Clock input –

4

GND

GND from operating
voltage

GND

Clock
– (GND)

Frequency
- externally
supplied

actual value

1

not used

2

Clock input +

2

Clock +

3

not used

4

Clock input –

4

Clock –

Pt 100
see infor-
mation**

actual value

1

not used

2

3
4

Pt 100

2

Process actual 1
(Power supply)

3

Process actual 3
(GND)

4

Process actual 2
(Compensation)

*

Can be adjusted via software

(see Operating Instructions,chapter „Specifying the standard settings“)..

Tab. 17: Terminal assignments of the process actual value input

** Connect the Pt 100 sensor via 3 cables for cable com-

pensation reasons.
It is essential to bridge Pin 3 and Pin 4 on the sensor.

When the operating voltage is applied, the process controller is
operating.

Now make the required basic settings and actuate the automatic
adjustment of the process controller. The procedure is described
in chapter “16.3 Start-up Type 8793”.