3 electrical installation profibus / devicenet – Burkert Type 8793 User Manual

Page 39

Advertising
background image

39

PROFIBUS DP / DeviceNet

Type 8792, 8793

15.3 Electrical Installation

PROFIBUS / DeviceNet

DANGER!

Risk of injury due to electrical shock!

▶ Before reaching into the device or the equipment, switch off the

operating voltage and secure to prevent reactivation!

▶ Observe applicable accident prevention and safety regulations

for electrical equipment!

WARNING!

Risk of injury from improper installation!

▶ Installation may be carried out by authorized technicians only

and with the appropriate tools!

Risk of injury from unintentional activation of the system and
an uncontrolled restart!

▶ Secure system from unintentional activation.

▶ Following installation, ensure a controlled restart.

NOTE!

Electromagnetic compatibility (EMC) is only ensured if the
appliance is connected correctly to an earthing point.
On the outside of the housing is a TE terminal for connection of
the technical earth (TE).
• Connect the TE terminal to the earthing point via a shortest pos-

sible cable (maximum length 30 cm).

15.3.1 X1 - M12, 8-pole circular connector

Pin Configuration

On the
device side

External circuit / Signal
level

1

not used

2

not used

Operating voltage
3

GND

3

24 V DC ± 10 %
max. residual ripple 10 %

4

+24 V

4

Input signals of the control centre (e.g. PLC)

5

Binary input +

5

+

0 ... 5 V (log. 0)
10 ... 30 V (log. 1)

6

Binary input –

6

GND (identical with Pin 3)

Output signals to the control centre (e.g. PLC) - (only used for
binary output option)

7

Binary output 1
(referring to Pin 3)

7

0 ... 24 V

8

Binary output 2
(referring to Pin 3)

8

0 ... 24 V

Tab. 18: Pin assignment; X1 - M12, 8-pole circular connecto PROFIBUS

DP / DeviceNet;

english

Advertising
This manual is related to the following products: