Electrical Installation

Type 8792, 8793

14.5.1 Connection board of the Type

8792/8793 with screw-type terminals

1
2
3
4

+24 V

GND

83 +
85 +
31 +

32 –

11 +

12 –

81 +

S +
S –
A
B

Optional:

Fig. 22: Designation of the screw-type terminals

Procedure:

Unscrew the 4 screws on the housing cover and remove the
cover.
The screw-type terminals are now accessible.

Connect Type 8792/8793.
The procedure is described in the following chapters.

14.6 Terminal assignment for cable

gland - positioner Type 8792

14.6.1 Input signals from the control centre

(e.g. PLC)

Terminal Configuration

On the device
side

External circuit / Signal
level

11 +

Set-point
value +

11 +

+ (0/4 ... 20 mA or 0 ... 5 / 10 V)
completely galvanically isolated

12 –

Set-point
value GND

12 –

GND Set-point value

81 +

Binary input
+

81 +

+

0 ... 5 V (log. 0)

10 ... 30 V (log. 1)

specific to operating voltage
GND (terminal GND)

Tab. 11: Terminal assignment; input signals of the control centre