Calibration menu, English – Burkert Type 8175 User Manual

Page 102

Advertising
background image

34

8175

ENGLISH

CALIBRATION MENU

0......9

ENTER

0......9

ENTER

ENTER

4.4.4 Gas Characteristics

In order for the 8175 level transmitter to find a precise measure of the level, the characteri-
stics of gas between the liquid and transmitter have to be defined.

-

If this value is not known either a default value can be applied or the characteristics can

be calculated by performing a 2 point Teach-In.

-

Within this option the values must be entered in m/s or ft/s depending on the type of

units selected (metric or imperial).

The default values for the gas characteristics are as follows:

Velocity of sound within the gas:

It is important that the velocity entered within this option is for the gas at
a temperature of 0°C.

Default value (air): 331.4 m/s within air at 0°C (32°F), if unit=cm or m

087.3 ft/s within air at 32°F (0°C), if unit=ft or inch

Temperature variation of the velocity:

Default value:

0.59 m/s / °C

0.075

ft/s

/

°F

If no temperature dependancy of the sound velocity is requested, calculate the sound velo-
city at ambiant temperature with the following equation:

V = 331.4 m/s + 0.59 m/s x T°C

Enter this calculated value and enter 0.00 as the temperature variation coefficient.

GAS COMP

331,4 m/S

322,7 m/S

T° =0.400

T° =0.590

ECHO

Temperature
variation
coefficient