Calibration menu, English – Burkert Type 8175 User Manual

Page 99

Advertising
background image

31

8175

ENGLISH

CALIBRATION MENU

4.4.3 Filter

Function

The function makes it possible to:

- activate the echo filtering and choose a damping level as well as a max. speed change
(FILTER 0 to 9)
- define the delay after which a failure is indicated by the outputs (DELA)
- select the type of tank (OPEN TAN, CLOSED or DOME(+)).

4.4.3.1 Filter 0 to 9

Echo Filtering:

Filters 0, 1 and 2: No echo filtering activated; The transmitter takes the nearest echo as the
level.

Filters 3 to 9: Echo filtering activated; The transmitter compares the echoes received with
those calculated within the ECHO menu so it can display the right level.

-

If no echo filtering is chosen, it is advised to select filter 0 during the Teach-In

calibration and after select the desired filter for the application.

-

If echo filtering is necessary, set the transmitter to filter 3 during calibration in order to

access this menu and after select the desired filter for the application.

ENTER

ENTER

0......9

ENTER

0......9

0......9

GAS COMP

OPEN TAN

CLOSED

DOME

DELA=000

DELA=300

FILTER 0

FILTER

FILTER 9

DOME+

Delay in
Seconds