INSTALLATION

8175 panel version 18-32VDC, wiring

Open the cabinet/cupboard and wire according to the pin assignment diagrams below.
The electronics within the 8175 allows a sourcing or sinking PLC to be connected. Position
A (Fig 3.11) provides a sourcing configuration and Position B (Fig 3.12) a sinking configu-
ration.

Fig. 3.11 Pin assignment, Position A

Fig. 3.12 Pin assignment, Position B

3.4.3 8175 panel version 18-32VDC

Connection of the 8170 sensor

-

Pass the cable through the wall / panel and use the cable gland to secure the cable.

-

Connect the coax and PT1000 temperature cables as shown in the diagram below.

-

Secure all the cables onto the protection plate as indicated via the 2 plastic ties

provided.

PT1000

Coax

Secure the cables
onto the protection
plate using the plastic
ties

Fig. 3.10 Panel cable
connections

4-20 mA

+

-

18-32 VDC

+

-

250 mA

I

-

+

4

3

2

1

(*)

4-20 mA

+

-

18-32 VDC

250 mA

I

-

+

4

3

2

1

+

-

(*)

PLC/control
valve or
positioner

SW 2,
Position A

SW 2,
Position B

PLC/control
valve or
positioner

ENTER

Locked

Unlocked

SW1

-

+

4

3

2

1

(*) If direct earthing is impossible, connect a 100 nF/50 V-condensator between the negative terminal of the power
supply and the earth.