Installation, English – Burkert Type 8175 User Manual

Page 86

Advertising
background image

18

8175

ENGLISH

INSTALLATION

-

+

4

3

2

1

8175 panel version, relay connection

The relay version is connected as follows :

Fig. 3.13 Pin assignment for relays

-

The device can be easily connected to a PLC independently of the respective version.

-

The ‘Enter‘ key can be locked by placing the SW 1 swich into the left position to avoid

accidental or unauthorized access.

3.4.4 8175 Wall Mounted Version 18-32VDC

Connection of the 8170 sensor

-

Open the cover after having unfasten the 4 screws on the front display.

-

Replace one of the housing cable glands through the cable gland inserted on the sensor

cable.

-

Connect the coax and PT1000 cables as shown in the diagram below.

Cable gland to remove

Fig. 3.14 Wall cable connections

4-20 mA

18-32 VDC

250 mA

3A

m

24VDC

115/230 VAC

3A

-

+

4

3

2

1

REL1

REL2

+

-

(*)

SW 1

ENTER

Locked

Unlocked

OR

(*) If direct earthing is
impossible, connect a
100 nF/50 V-condensa-
tor between the negative
terminal of the power
supply and the earth.