Test menu, English – Burkert Type 8175 User Manual

Page 119

Advertising
background image

51

8175

ENGLISH

TEST MENU

0......9

ENTER

ENTER

4.5.1 Offset

Compensation

Within this option the user has the possibility of correcting the basic setting of 4 mA
generated by the transmitter. The transmitter generates a value of 4mA by pressing

ENTER

when «OFFSET» is displayed within the main test menu.

Measure the generated current with an ammeter. If the displayed value is incorrect it can be
corrected by entering the measured value on the ammeter.

4.5.2 Span

Compensation

Span compensation provides the option of changing the basic setting of 20 mA. The
procedure is identical to that of the offset compensation above. The transmitter generates
20mA if the key

ENTER

is pressed when «SPAN « is displayed within the main test menu.

Measure the generated current with an ammeter. If the displayed value is incorrect it can be
corrected by entering the measured value on the ammeter.

Enter the measured value

Enter the measured value

SP= 19.96

T° ADJUST

SPAN

SP= 20.00

0......9

ENTER

ENTER

OF= 04.02

SPAN

OFFSET

OF= 04.00

Advertising
This manual is related to the following products: