15

8175

ENGLISH

INSTALLATION

4-20 mA

+

-

18-32 VDC

+

-

250 mA

I

-

+

4

3

2

1

(*)

4-20 mA

+

-

18-32 VDC

250 mA

I

-

+

4

3

2

1

+

-

(*)

4-20 mA

18-32 VDC

250 mA

3A

m

24VDC

115/230 VAC

3A

-

+

4

3

2

1

REL1

REL2

+

-

(*)

SW 2,
Position A

SW 2,
Position B

Fig. 3.7 Pin assignment for relays

PLC/control
valve or
positioner

ENTER

Locked

Unlocked

SW1

SW 1

ENTER

Locked

Unlocked

OR

3.4.2 8175 compact version

Wiring of the 18-32 VDC version, with cable gland
Remove the cover via the screws on the front display and pull the cable through the cable
gland and wire according to one of the pin assignment diagrams below.
The electronics within the 8175 allows a sourcing or sinking PLC to be connected. Position
A (Fig 3.5) provides a sourcing configuration and Position B (Fig 3.6) a sinking one.

Fig. 3.5 Pin assignment, Position A

Fig. 3.6 Pin assignment, Position B

Relay connection of the 18-32 VDC version, with cable gland
The electrical wiring of this model is possible via the use of 2 cable glands. Remove the
cover via the screws on the front display and pull the cables through the cable glands and
wire according to pin assignment diagram below (Fig. 3.7).

-

The device can be easily connected to a PLC independently of the respective version.

-

The ‘Enter‘ key can be locked by placing the SW 1 swich into the left position to avoid

accidental or unauthorized access.

(*) If direct earthing is
impossible, connect a
100 nF/50 V-condensa-
tor between the negative
terminal of the power
supply and the earth.

PLC/control
valve or
positioner