8175

ENGLISH

INSTALLATION

-

Do not open and wire the transmitter with the power supply connected.

-

It is obligatory to put security devices close to the transmitter, on:

Power supply : 18-32VDC - 250mA fuse and interrupter

115/230VAC - 5A fuse and a bipolar interrupter

Relay :

3A fuse max. and a bipolar interrupter

(depending

on

the

application).

-

Do not apply both a dangerous voltage and a very low safety voltage to

the

relays.


3.4.1 8175 Compact version with an EN 175301-803 connector

Wiring

-

+

4

3

2

1

1

3

2

+ -

EN 175301-803

(*)

1. To open the connector remove screw 1 (Fig. 3.3).
2. Remove the internal part 3 from the external casing 2.
3. Connect the transmitter according to the pin

assignment in Fig. 3.3

4. When re-assembling, the internal part 3 can be rotated

in 90° steps to a desired position before inserting back
into the casing 2.

5. Tighten the cable gland 5. Then place gasket 4

between the EN 175301-803 connector and the fixed
connector of the transmitter and plug the
EN 175301-803 connector onto the transmitter.

6. Tighten screw 1.

Fig. 3.3 Plug assembly

I (4-20 mA output)

Orange

Red

Black

Brown

Green/Yellow

To the earth lug of the housing

Power supply

+ (L+; 18-
32 VDC)

- (L-)

To position SW2,
see 3.4.2, compact
version with cable
gland

(*) If direct earthing is
impossible, connect a
100 nF/50 V-condensa-
tor between the negative
terminal of the power
supply and the earth.