Calibration menu, English – Burkert Type 8175 User Manual

Page 114

Advertising
background image

46

8175

ENGLISH

CALIBRATION MENU

4.4.7 Output

Current

Within this option the measuring range can be defined corresponding to the output current
of 4-20 mA.

-

The beginning of the

measuring range might be larger than the end creating an

inverted signal, e.g. 0.5 to 6m corresponds to 20-4 mA.

-

The engineering units and decimal point selected will be valid within this option.

-

The basic setting of the span and offset can be checked within the test menu.

0......9

ENTER

0......9

ENTER

ENTER

Enter the beginning of the
measuring range

Enter the end of the measuring range

-

In case of signal loss the device will emit an error signal of 22mA.

-

The diagram below shows the type of relationship between the 4-20mA ouptut and the

associated measuring range.

CURRENT

RELAY

4=00.00

4=02.00

20=00.00

20=12.00

2

20

mA

4

12

m