3.3 18-32 VDC ELECTRONIC CARD IDENTIFICATION

-

The Coax cable and PT1000 connections must be connected in all cases to ensure the

device functions correctly.

-

The

ENTER

key can be locked to avoid accidental or unauthorised access by placing

SW1 in the left position in the diagram above.

3.4 GENERAL ELECTRICAL CONNECTION

-

Use cables with a temperature limit of 80°C minimum.

-

For normal operating conditions the measuring signal can be transmitted by a simple

cable of 0.75 mm

2

cross section.

-

The line must not be installed in combination with carrying lines with a higher voltage or

frequency. If a combined installation cannot be avoided, a minimum space of 30 cm

(1 ft) or shielded cables should be adopted.

-

When using shielded cables observe faultless grounding of the shield.

-

For EMC purposes,the earth must be connected via the earth lug on the side of the

enclosure (see fig. 3.2). This point must be connected locally to a good earth.

-

The cable diameters for the cable gland versions must respect the following:

Compact: between 6-12mm and 6 mm with a multiway seal

Wall mounted: between 4-8mm (not used cable glands must be blanked off).

-

In case of doubt, always use shielded cables.

-

The 18-32 VDC power supply must be filtered and regulated - section 6.1.

SW 2 - Sourcing or
sinking configuration.

Terminal connections -
Connection of power supply
of 18-32VDC and 4-20mA
output.

SW 1 - Locking of the
‘Enter‘ key to avoid
accidental or unau-
thorised access to the
calibration and test
menus.

Sensor Coax cable
connection.

PT1000 connection.

Relay connections - Connection of relays 1 & 2 (optional).

-

+

4

3

2

1

ENTER

Locked

Unlocked