Output port control, Ven in section 9.9 – CTI Products RCD Standard - Remote Comparator Display User Manual

Page 85

Advertising
background image

MCN Remote Comparator Display

Appendix A

CTI Products, Inc.

Changing Status Message Text

68-10856-210

79

Note

#

(Nx)

Octave

(Ox)

Note Standard

Musical

Note

Freq

Hz

76

6

D+

D# 8

4978

77

6

E

E 8

5274

78

6

F

F 8

5588

79

6

F+

F# 8

5920

80

6

G

G 8

6272

81

6

G+

G# 8

6645

82

6

A

A 8

7040

83

6

A+

A# 8

7459

84

6

B

B 8

7902

Table 6 - Audio String Notes

9.9 Output Port Control

The output port control field allows you to specify a output port control
sequence to execute when the status message text is displayed. The output control
sequences are specified under the heading <OUTPUT> in the MCNRCD.CFG
file. The format of these sequences is the following:

port # mask control

NOTE: The MCNRCD software requires that any output port being used with
this output port control must be a read/write port. The MCNRCD software reads
the current value of the port by doing an input of the port address.

The three fields of each line under this heading are the following:

1.

The port # field is a 3 digit HEX value that specifies the address of the output

port that will be modified.

2.

The mask field is a 2 digit HEX value that clears bits in the current output port

value (this value is logically AND’ed with the current output port value).

3.

The control field is a 2 digit HEX value that sets bits in the current output port

value (this value is logically OR’ed with the current output port value).

The control sequence is

new value = (current value AND mask) OR control

The example MCNRCD.CFG file shown in Figure 32 defines 17 different output
control sequences that can be executed. To execute an output control sequence,
simply set the output port control field of the status message text definition line to
the output port sequence number. The first sequence under the <OUTPUT>