Micro-PWC CONFIGURATION GUIDE

Grafx Editor 127

selected. If the attribute has a text entry box, a blinking cursor will appear in that entry box and the desired
value, expression, or variable can be entered. If neither portion of the attribute setting box is clicked on, the
attribute will remain unaffected. If the attribute is selected but no entry is made in the entry box, the
attribute definition will use the attribute's default value.

Each attribute has a default value, and (except for the Text attribute, and some Blink and Spin attribute
parameters) a minimum and maximum permitted value. The default value is used when the attribute's
entry box has been clicked on but no entry is made, or when the value entered is outside the range of the
permitted values (less than the minimum or greater than the maximum). Default values for the attributes
are as follows.

Note

It is possible to configure dynamic attributes which are unnecessary
for an object; configuration of such items will have no effect on the
object. For example, if the object is a straight line, and the Filled
attribute is configured, it will have no effect on the appearance of
the line.

Table 4-6. Attribute Default Values

ATTRIBUTE

DEFAULT

MINIMUM

MAXIMUM

Text

Empty string ("")

none

none

Visible

1 (visible)

0

1

Filled

1 (filled)

0

1

Fill Color

0 (black)

0

95

Line Color

0 (black)

0

95

Text Color

0 (black)

0

95

Line Style

1 (solid line)

0

4

Line Width

1 (narrow)

1

4

Pattern

1 (solid fill)

1

4

Blink Period

5 (tenths of a second)

1

none

Blink Phase

0 (Blink Periods)

0

none

Blink Color 1

1 (white)

0

95

Blink Duration 1

1 (Blink Periods)

1

none

Blink Color 2

0 (black)

0

95

Blink Duration 2

1 (Blink Periods)

1

none

Steady Color

7 (white)

0

95

Spin Period

5 (tenths of a second)

3

none

Spin Angle

20 (degrees)

-180

+180

Advertising