10.3.2 Historical Block Legend

Click in the Legend entry box to enter the string which is to be used as the legend for the Historical Data-
base Point under configuration. This legend can be up to 63 characters in length.

10.3.3 Period and Start Time

Both the Period (user-defined collection interval) and the Start Time (which defines the beginning of the
Period) are entered in the same entry box. The Period is entered first; the words daily, weekly and
monthly are valid entries to define the Period. Alternatively, the user can define a customized Period by
defining the number of days, hours, minutes and seconds in the Period using the following format (leading
zeros are required with single digit entries):

DD:HH:MM:SS

(The minimum recommended period is 30 seconds.) Enter a comma (,) after the Period to separate it from
the starting time. After the period has been defined, the starting time (hours, minutes, seconds) and date
(day, month, year) which mark the beginning of the interval, are entered in the format:

HH:MM:SS DD-MMM-YY

The default Period is hourly (00:01:00:00) and the default Start Time is midnight of the current day (e.g.,
00:00:00 30-JUN-07).

TC00582A

Figure 10-2. Historical Block Configuration Window

Note

The 24 hour clock is used, and the month is identified by the first
three letters of the month name (in English).