1 configuring the triggering tagname, 2 specifying the target display, 2 specifying a point display – Micromod Micro-PWC: 53PW6000 MicroPWC Configuration Guide User Manual

Page 50

Advertising
background image

Micro-PWC CONFIGURATION GUIDE

30 System Configuration

Message Review

Printer Review

Event History

Below the Display Type list box are two blank fields, Display Type and Index. Below these fields are two
text entry boxes. The first entry box is Tagname, the second appears to the right of, and is used in conjunc-
tion with, a Find button.

To assign an Alarm Vector to a tagname, first configure the tagname, then specify the target display. This
procedure is described below.

2.8.0.1 Configuring the Triggering tagname

When the Alarm Vector Configuration window appears, the Tagname entry box is automatically highlighted
and ready to accept input. Enter the tagname for which vectoring is being assigned.

When configuration of both the tagname and display type has been completed for the alarm vector, the
tagname will be inserted into the Tagnames list box, in alphabetical order. The list will shift within the list
box so that the newest entry is displayed at the top of the list box.

2.8.0.2 Specifying the Target Display

Once a tagname has been entered in the Tagname entry box or selected from the Tagnames list box,
select the display which will be used when that tagname is in alarm and the Vector button is clicked.
Vector buttons are located on the alarm lines in the Mini-Alarm Window and on each line of the Alarm
Review display.

Click on the desired type in the list box labelled Select Vector Display Type. The selection will be high-
lighted and will automatically be displayed in the field labelled Display Type.

2.8.0.2.1 Specifying Graphic, Summary, Group, Point, or Trend Displays

If Graphic, Summary, Group, Point, or Trend has been selected as the Display Type, more than one dis-
play is available for that type. A window will appear to aid the user in specifying the index of the desired
display. In the case of Graphic, Summary, Group, and Trend display types, the window which appears will
be similar to the example in

Figure 2-13

.

Use the scroll bar and the

U

P

and

D

OWN

A

RROWS

to view the list of available displays for the selected display

type. If all or part of the title is known, enter it in the Title entry box, then click Search. If found, the item will
be highlighted at the top of the list box. Similarly, if the index number is known, enter it in the Index entry
box, then click Search to locate it in the list, or click OK to make the selection.

To move quickly to the first item in the list box, click Top. When the desired display has been selected, click
OK.

2.8.0.2.2 Specifying a Point Display

If Point has been selected as the Display Type, a much simpler window will appear. The Point Selection
window consists of an Enter Tagname entry box, and OK, and Cancel buttons. Enter the tagname of the
point in the entry box, then click OK. If a tagname has been specified, use of the Vector button will cause
the point display associated with the specified tagname to appear. This allows the user to vector to a point
display other than that of the point which is in alarm.

Note

No warning will be given if the tagname does not exist; the string
will be accepted and entered into the Tagnames list box.

Advertising