Watlow Series 146 Retrofit User Manual

Page 5

Advertising
background image

These notes are used to signify areas of concern in changing to a retrofit choice. These notes are also printed at the end
of the retrofit listing.

Note 1: Retrofit controller requires a substitution of a 100 Ohm RTD sensor for the thermistor.
Note 2: Mounting and dimensions of retrofit controller are different. Verify that sufficient panel space and depth is

available.

Note 3: Retrofit controller outputs are different. Add external interposing mechanical or solid state relay if applicable.
Note 4: Retrofit controller has a programmable, not fixed set point. Lock set point using controller's lockout parameter.
Note 5: For DIN rail mounting or sub-panel mounting, purchase DIN rail adapter p/n 0822-0586-P001 for 1/32 DIN or

p/n 0822-0586-P002 for 1/16 DIN.

Note 6: Add a suppressor, Watlow p/n 0804-0147-0000, for inductive loads.
Note 7: Retrofit does not have equivalent action (as example, no manual reset)
Note 8: Retrofit controller does not have dual dial scale.
Note 9: Hardware lockout is not available on retrofit.
Note 10: Retrofit controller does not have user selectable line voltage.
Note 11: Retrofit does not support remote set point or retransmit. Check if pins 13, 14, 15 or 16 have termination. If

wires are on these pins, select a different retrofit.

Note 12: Retrofit controller does not have user selectable control action.
Note 13: Solid state sensor required for humidity. See

http://www.vaisala.com

Note 14: Retrofit controller does not have user selectable control mode.
Note 15: Use auxiliary event board A007-1732-F4B8
Note 16: Retrofit communications are different, consult specifications.
Note 17: Verify retrofit input range matches application.

Advertising