Agency Listings, Approvals, and Requirements

53688

2-3

commission, public service commission or corporation commission for information.

j) If your home has specially wired alarm equipment connected to the telephone line, ensure

the installation of this MS-25 does not disable your alarm equipment. If you have
questions about what will disable alarm equipment, consult your telephone company or
qualified installer.

Electrical Safety Advisory:

Parties responsible for equipment requiring AC power should consider including an advisory
notice in their customer information suggesting the customer use a surge arrestor. Telephone
companies report that electrical surges, typically lightning transients, are very destructive to
customer terminal equipment connected to AC power sources. This has been identified as a
major nationwide problem.

2.2

Underwriters Laboratories (UL)

2.2.1

Requirements for All Installations

General requirements are described in this section. When installing an individual device, refer
to the specific section of the manual for additional requirements. The following subsections
list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on).

1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.

2. Use ONLY the addressable smoke detectors specified in Section 5.1 of this manual.

3. Use UL listed notification appliances compatible with the MS-25, choose from those spec-

ified in the Appendix at the back of this manual.

4. A full system checkout must be performed any time the panel is programmed.

Restricted Options:

The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 -
30 hours. For UL certified installations this number must be set from 1 to 3 hours.

The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL
certified installations the setting must be a maximum of 60 seconds.

Call forwarding shall not be used.

Waterflow and Supervisory have to be set to Latching as shown in the restricted options
table in Section 6. See Table 6-1:.