Trouble Shooting and Quick Tips

53688

9-3

“AC” indicates AC power supply trouble

“nC1” indicates notification appliance circuit 1 trouble

“nC2” indicates notification appliance circuit 2 trouble

“tSt” indicates a trouble for the duration of a walk test

Correct the fault and the trouble will restore

9.2

Web Server Menus

The System Summary and Mapping Table sections are not editable, but are populated based
on the entries in the other sections.

9.2.1

To add a smoke detector:

Which zone will it be in? (e.g. the Lunchroom, Zone 2)

1. Click on Zone Programming, under Zone 2

2. Click Alarm Points

3. Find an Unused SLC Address and click on the detector type (e.g. address 24 Photo)

4. Click Accept

Note: Remember to choose to Download to Panel after all of your changes are done AND set the rotary switches

on the back of the smoke detector. (e.g. tens=2 and ones=4)

9.2.2

To add a notification appliance (fire bell)

1. Click on NAC Programming

2. Click on the NAC circuit you want to activate (e.g. NAC 1)

3. Click to check the box for either Alarm and/or Supervisory events to cause that NAC to

activate.

9.2.3

To add a Remote Annunciator (DIP switch address 1
or 2)

1. Click on System Options

2. Click on yes option for Remote Annunciator Installed 1/ Remote Annunciator Installed 2.

3. Click Accept

Note: Remember to choose to Download to Panel after all of your changes are done.