Model MS-25 Installation and Operation Manual

9-4

53688

9.2.4

To add custom Zone name

1. Click on Zone Programming

2. Click on Zone Options. Enter custom Zone name (20 characters max) in the corresponding

field.

3. Click Accept

Note: Remember to choose to Download to Panel after all of your changes are done.

9.2.5

To trip an SLC notification appliance

1. Click on Output Point Programming

2. Click on the tab for the event type you want to activate the notification appliance.

3. Click the circle for Present across from one or both of the SLC device(s) addresses for the

Zone which has the initiation devices that you want to trip the appliance.

Note: Be sure to set your SLC notification device address to match.

9.2.6

To trip a Door Holder

1. Click on Output Point Programming

2. Click on the System tab

3. Click on the circle for Present across from the SLC Address of the door holder. (e.g. 158)

4. Set the Door Holder device address accordingly. (e.g. 158)

The Door Holder will provide 24VDC when in standby, 0V during alarms or loss of AC.

An on board relay can also be used for Door Holder power. See Section 6.6.5.

Help to reduce false alarms

In the System Options section, Water Flow Delay can be adjusted to account for brief periods
of water pressure fluctuation.

Alarm Verification Time verifies an alarm condition by resetting the smoke detectors before
activating alarms (UL 864 installations must not exceed 60 seconds).