Model MS-25 Installation and Operation Manual

6-4

53688

6.3.4

Maximum SLC address point count

The MS-25 control panel supports a maximum of 25 SLC points to be used within the 159
point address range. The points can be all inputs, all outputs or any combination of inputs and
output points. When more than 25 SLC devices are added to the control panel, any excess
points will indicate a trouble and not be recognized by the panel.

6.3.5

Installer Code

The installer code is factory programmed as 123456. The installer code is required to learn
and remember which SLC devices are connected to the panel. The installer code can be
changed when a PC is used to modify the default programming options.

6.4

JumpStart Auto Programming

Once the physical installation of SLC devices is finished, the panel will need to learn which
SLC devices and SBUS annunciators are present.

To run JumpStart:

1. Press and hold the “JumpStart” key,

2. Press the installer code after PIN is displayed.

3. During JumpStart, the panel will briefly light up all LEDs and then display “SLC Prg” on

the 7 segment display.

4. When complete the display will be off and programming is complete.

If changes are required that affect address settings for the SLC devices, device types or
number of SLC devices installed you will need to repeat JumpStart to re-learn which devices
are supposed to be present on the system.

IMPORTANT!

There is no limit to how often you can run JumpStart. Each time you run this

process it starts fresh and does not remember previously installed devices

that are no longer present.