2 control panel programming, 3 default control panel configuration, 1 default mapping of slc inputs to outputs – Fire-Lite MS-25E Addressable Fire Control Panel User Manual

Page 60: 2 mapping of slc inputs to outputs, Control panel programming -2, Default control panel configuration -2

Advertising
background image

Model MS-25 Installation and Operation Manual

6-2

53688

6.2

Control Panel Programming

The MS-25 is an addressable control panel that has the characteristics of a 5 zone
conventional fire alarm control panel.

6.3

Default Control Panel Configuration.

The panel ships from the factory in a defaulted configuration that may allow the installer to
use the panel without doing any custom programming.

6.3.1

Default Mapping of SLC Inputs to Outputs

The panel mapping configuration for the MS-25 is fixed with regards to SLC addresses, zone
assignments and output points. The relationship between input points and output points
follows the rules defined in 6.3.2 below. For input points, the SLC address determines the
zone assignment and alarm characteristics. For output points, the SLC address determines the
output function for the point.

6.3.2

Mapping of SLC Inputs to Outputs.

Table 6-2: Input Points

INPUT POINTS

Zone

Input Point Types

Function

Qty

Start

SLC ID

End SLC

ID

Description

Zone 1

HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,
BG-12LX, HFS-MM

Alarm

15

1

15

Alarm Zone 1

Supervisory 5

16

20

Supervisory Zone 1

Zone 2

HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,
BG-12LX, HFS-MM

Alarm

15

21

35

Alarm Zone 2

Supervisory 5

36

40

Supervisory Zone 2

Zone 3

HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,
BG-12LX, HFS-MM

Alarm

15

41

55

Alarm Zone 3

Supervisory 5

56

60

Supervisory Zone 3

Zone 4

HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,

BG-12LX, HFS-MM

Alarm

15

61

75

Alarm Zone 4

Supervisory 5

76

80

Supervisory Zone 4

Zone 5

HFS-P, HFS-PT, HFS-D,
HFS-T, SD355, SD355T,
D355PL, H355, MMF-301,
BG-12LX, HFS-MM

Alarm

15

81

95

Alarm Zone 5

Supervisory 5

96

100

Supervisory Zone 5

Advertising