2 ac power connection, 1 ac power connection for ul 864 applications, Ac power connection -4 – Fire-Lite MS-25E Addressable Fire Control Panel User Manual

Page 34: 1 ac power connection for ul 864 applications -4

Advertising
background image

Model MS-25 Installation and Operation Manual

4-4

53688

4.2

AC Power Connection

4.2.1

AC Power Connection for UL 864 applications

At installation, connect the AC terminals to the power source as shown in Figure 4-2. It may
be necessary for a professional electrician to make this connection. Connect black and white
wires from transformer to 120V power. Connect ground wire from 120V power to screw
labeled G on the MS-25 circuit board.

The AC power input is rated at 120 VAC, 60 Hz, 1.5A for MS-25 and 230 VAC, 50/60Hz,
.75A for MS-25E.

Figure 4-2 120/230 VAC Power Connection

Ground

To AC

Supervised
AC
Connection

Advertising