7 configuring module, 1 assigning module ids, Configuring module -13 – Fire-Lite MS-25E Addressable Fire Control Panel User Manual

Page 43: 1 assigning module ids -13, Section 4.7.1)

Advertising
background image

Control Panel Installation

53688

4-13

4.7

Configuring Module

This section describes how to configure the ANN-80 Annunciator that has been added to the
system. Each SBUS device requires a unique address. ANN-80 Series DIP switch S21 is used
to set the address. This address will be displayed on the LCD display as the Station ID
number.

4.7.1

Assigning Module IDs

When installing the ANN-80 you must use the DIP switches on the module to assign an ID# to
the module. A maximum of 2 devices can be connected to the FACP SBUS communication
circuit. The SBUS device address needs to be set to 01or 02.

Note: Note that 00 is not a valid address.

Figure 4-9 shows the DIP switch positions and their correlation to a numerical ID.

Figure 4-9 DIP switch settings

ID Number
(Address)

(not valid) 00

01

02

DIP Switch

Advertising
This manual is related to the following products: