Model MS-25 Installation and Operation Manual

3-2

53688

3.3

Electrical Specifications

Table 3-1 list the electrical specifications for the MS-25 field wiring as well as a description of
the each individual terminal and their respective electrical rating. For location of the terminals
refer to 3.5. See also Section 4 for installation.

*

Regulated for NAC circuits

*

Special application when used for auxiliary power circuits.

Table 3-1: Terminal Descriptions

Terminal

Block

Label

Description

Rating

Earth Ground

Fault Impedance

Group

Individual

Voltage

Current

Ohms

TB 1

SBUS

SBUS Power

27.4 VDC

100 mA

0

Ω

+

A

SBUS Communication

3.3 VDC

10 mA

0

Ω

B

SLC Out

SLC Terminals

24 VDC

100 mA

0

Ω

+

*NAC1

Notification Appliance Circuit 24 VDC

2.0 Amp

0

Ω

+

Auxiliary power

1.0 Amp

*NAC2

Notification Appliance Circuit 24 VDC

2.0 Amp

0

Ω

+

Auxiliary power

1.0 Amp

TROUBLE NO

Normally open relay contact

24 VDC

2.5 A, resistive

N/A

COM

Common terminal

NC

Normally closed relay contact

RELAY 1

NO

Normally open relay contact

24 VDC

2.5 A, resistive

N/A

COM

Common terminal

NC

Normally closed relay contact

RELAY 2

NO

Normally open relay contact

24 VDC

2.5 A, resistive

N/A

COM

Common terminal

NC

Normally closed relay contact

TB 2

TELCO 1

RING

Phone Line 1 Telco Ring

N/A

N/A

N/A

TIP

Phone Line 1 Telco Tip

PHONE 1

RING

Phone Line 1 Phone Ring

TIP

Phone Line 1 Phone Tip

TELCO 2

RING

Phone Line 2 Telco Ring

TIP

Phone Line 2 Telco Tip

PHONE 2

RING

Phone Line 2 Phone Ring

TIP

Phone Line 2 Phone Tip