Table 6-2 shows that any input SLC device with an address set within the range 1-15 will be
assigned to zone 1 as an alarm input type. An SLC output relay point assigned to address 111
or 112 will activate for an alarm in zone 1.

6.3.3

Default Mapping for the 2 built-in Notification
Circuits.

There are 2 built-in notification circuits (NAC 1 and NAC 2). They are both defaulted to
activate when any of the 5 zones are in alarm. When active, NAC 1 and NAC 2 will sound the
System Sensor synchronization pattern. To change the behavior of the default mapping of
these circuits refer to Section 6.5.

Table 6-3: Output Points

OUTPUT POINTS

Group

Output Point Type

Qty

Start SLC

ID

End SLC

ID

Output Activates For

OPG 1

HFS-MR, CRF-300, CRF-300A

2

111

112

Zone 1 Alarm

OPG 2

HFS-MR, CRF-300, CRF-300A

2

113

114

Zone 2 Alarm

OPG 3

HFS-MR, CRF-300, CRF-300A

2

115

116

Zone 3 Alarm

OPG 4

HFS-MR, CRF-300, CRF-300A

2

117

118

Zone 4 Alarm

OPG 5

HFS-MR, CRF-300,CRF-300A

2

119

120

Zone 5 Alarm

OPG 6

HFS-MR, CRF-300, CRF-300A

2

121

122

Zone 1 Supervisory

OPG 7

HFS-MR, CRF-300, CRF-300A

2

123

124

Zone 2 Supervisory

OPG 8

HFS-MR, CRF-300, CRF-300A

2

125

126

Zone 3 Supervisory

OPG 9

HFS-MR, CRF-300, CRF-300A

2

127

128

Zone 4 Supervisory

OPG 10

HFS-MR, CRF-300, CRF-300A

2

129

130

Zone 5 Supervisory

OPG 11

HFS-MR, CRF-300, CRF-300A

2

131

132

Zone 1 Trouble

OPG 12

HFS-MR, CRF-300, CRF-300A

2

133

134

Zone 2 Trouble

OPG 13

HFS-MR, CRF-300, CRF-300A

2

135

136

Zone 3 Trouble

OPG 14

HFS-MR, CRF-300, CRF-300A

2

137

138

Zone 4 Trouble

OPG 15

HFS-MR, CRF-300, CRF-300A

2

139

140

Zone 5 Trouble

OPG 16

HFS-MR, CRF-300, CRF-300A

2

141

142

General Alarm

OPG 17

HFS-MR, CRF-300, CRF-300A

2

143

144

General

Supervisory

OPG 18

HFS-MR, CRF-300, CRF-300A

2

145

146

General Zone Trouble

OPG 19

HFS-MR, CRF-300, CRF-300A

2

147

148

General Trouble

OPG 20

HFS-MR, CRF-300, CRF-300A

2

149

150

Alarm Silenced

OPG 21

HFS-MR, CRF-300, CRF-300A

2

151

152

Trouble Silenced

OPG 22

HFS-MR, CRF-300, CRF-300A

2

153

154

AC Loss

OPG 23

HFS-MR, CRF-300, CRF-300A

2

155

156

Resettable Aux Relay

OPG 24

HFS-MR, CRF-300, CRF-300A

2

157

158

Aux Door Holder