Model MS-25 Installation and Operation Manual

6-8

53688

6.6.2

Zone Programming

6.6.2.1 SLC Addresses Within Each Zone

Each zone has 15 alarm SLC addresses and 5 supervisory SLC addresses assigned to it as
described in table 6.1. For each SLC address within a zone, the SLC device type choices are
Unused, Detector, Manual Pull Switch, Latching Water Flow Switch or Non-Latching Water
Flow Switch. The default setting is that all points are unused.

6.6.2.2 Zone Silenceable

When an alarm occurs within a zone, there is a programming option that allows the outputs to
be silenceable or not. If you want the SILENCE key to be able to silence outputs triggered by
active alarms within the zone select YES for this option. The default setting is Yes.

6.6.2.3 Zone Type

A zone can be either a one count zone or an alarm verification zone. The default setting is one
count. A one count zone has an immediate alarm when a single detector goes into alarm.

Alarm verification is an optional false alarm prevention feature for smoke detectors that
verifies an alarm condition by resetting the smoke detector. If the alarm condition still exists
by the time the reset cycle has completed, the detector will go into alarm. If the detector is no
longer in alarm, the initial alarm is ignored. The alarm verification sequence for a detector
does not occur if the zone is already in alarm.

6.6.3

Output Point Programming

For each output SLC address you can select that a device is present or unused. The default
setting for all output points is unused.