4 notification appliance circuit (nac) programming, 1 circuit function, 2 conventional notification circuit mapping – Fire-Lite MS-25E Addressable Fire Control Panel User Manual

Page 67

Advertising
background image

Programming

53688

6-9

6.6.4

Notification Appliance Circuit (NAC) Programming

6.6.4.1 Circuit Function

The two notification circuits are both defaulted to activate the System Sensor synchronization
pattern when any of the five zones are in alarm. You can define each of the notification
circuits to be either a conventional notification circuit or an auxiliary power type circuit.

6.6.4.2 Conventional Notification Circuit Mapping

When defined as a conventional notification circuit, the circuit can be configured to activate
for any combination of zone alarms and/or supervisories. Select all the categories you wish to
have the circuit activate under.

Conventional Notification Circuit Cadence Pattern

When a conventional notification circuit activates, it can be configured to produce one of six
output patterns.

1. Constant On - 24V DC power

2. ANSI - ANSI temporal pattern

3. AMSECO Sync - Strobe synchronization for AMSECO appliances

4. Gentex Sync - Strobe synchronization for Gentex appliances

5. System Sensor Sync - Strobe synchronization for System Sensor appliances

6. Wheelock Sync - Strobe synchronization for Wheelock appliances

Auxiliary Power Options

Each of the notification circuits can be configured as an auxiliary power circuit in one of three
options.

1. Constant - Always on, 24V DC power.

2. Door Holder - 24V DC when in standby, Off if any alarm device activates, or loss of AC

power.

3. Resettable - 24V DC except for 30 seconds off during panel reset.

Advertising
This manual is related to the following products: